Intro to
Basic Fire Alarm
Technology

Silent Knight :: 7550 Meridian Circle :: Maple Grove, MN 55369 :: 800-328-0103

1
Basic Fire
Let’s examine the
components that
make a basic Fire
Alarm Control
System.
2
Main Controller
• The brains of the
system
• Provides power to the
system, monitors
inputs and controls
outputs through
various circuits
• Performs other
functions as required
by the appropriate
code
3
Elements of a Control Panel
Requires two Power Sources

Primary
(AC)

Secondary
(DC)
4
Elements of a Control Panel
Inputs

A fire alarm
system can
have a variety of
input devices.
Smoke Detector

Manual Pull Station

5
Inputs
• Initiating Device: A system component that
originates transmission of a change of state
condition, such as a smoke detector,
manual fire alarm box, supervisory switch,
etc...
• Initiating Device Circuit (IDC): A circuit to
which automatic or manual initiating
devices are connected where the signal
received does not identify the individual
device operated
6
Elements of a Control Panel
Outputs

Horns

Strobes

7
Outputs
• Notification Appliance: A fire alarm
system component such as a bell,
horn, speaker, light, or text display
that provides audible, tactile, or visible
output, or any combination thereof.
• Notification Appliance Circuit: A
circuit or path directly connected to a
notification appliance.
8
The Basic System
Main Controller

Inputs

Primary
(AC)

Outputs
Secondary
(DC)

9
Basic Fire Alarm Technology
• Signal Initiation/Initiating Devices
 Need to understand stages of fire and
what technology works best for each

10
The Stages of a Fire
• Stage One
 Incipient: Products of Combustion
particles are produced (<0.3 microns).
No visible smoke or detectable heat.
May occur for milliseconds or days.
• Use ionization detectors

11
The Stages of a Fire
• Stage Two
 Smoldering: Visible smoke particles are
produced (>0.3 microns). Little visible
flame or noticeable heat.
• Use Photoelectric Detectors

12
The Stages of a Fire
• Stage Three
 Flame: Rapid combustion produces
radiant energy in the visible, and invisible
(IR, UV) spectrums. Heat begins to
buildup at this stage
• Use Spark or Flame Detectors

13
The Stages of a Fire
• Stage Four
 High Heat: Uncontrolled combustion is
caused by the heating of nearby
combustibles to their ignition point.
• Use Heat Detectors

 Note! Major disadvantages of using
thermal energy for fire identification are
• Takes a while for a fire to be recognized
• The toxic gases that are produced before an
alarm point is reached
14
Types of Detectors
• Photoelectric



•
•
•

Light Scattering
Light Obscuration

Ionization
Duct
Heat (Thermal)

15
Photoelectric Smoke
Detectors:
Light-Scattering Type

• Uses a Light-Emitting Diode (LED) that
sends a beam of light into a dark chambera photo diode sits on the other side of a
partition within the chamber  
• Smoke particles entering the chamber
deflect some of the light rays into the photo
cell. The photo cell generates a current
when exposed to light, and if the current
reaches a certain level, the detector
alarms.
16
Photoelectric Smoke Detectors:
Light Obscuration Type

• In a projected Beam
Detector, alarms are
generated by diffusing
the projected light
beam by a specified
percentage of
obscuration.
• Total beam blockage
generally results in a
trouble signal.

17
Ionization Smoke Detectors
• Contain a small amount of radioactive
material encapsulated in a metal
chamber. Ionizing radiation develops
a low, but steady electrical current. 
Smoke particles entering the chamber
disrupt the current and trigger the
detector's alarm. 
• Ion detectors react more quickly to
fast flaming fires that give off little
smoke.
18
Heat Detectors
• Fixed Detectors:

 Alarm when the sensing element reaches a certain set
point.
 Two common models have 135 and 200-degrees F
range.
 Fixed element is generally a non-restorable type, and
when activated, must be replaced.

• Rate-of-Rise Detectors:

 Respond when the rate of temperature increase is
greater than an allowable limit (15 degrees in 60 secs.)
(placement in a stable environment) (e.g.. ovens, heating
vents, etc.).
 The Rate-of-Rise element is restorable when conditions
return to normal.

• Rate Compensation will respond regardless of the
rate of temperature rise.

19
Duct Detectors
• Photoelectric detector
mounted in housing
outside the ductwork
that has probes that
extend into the duct to
sample the air inside
the duct.
• Primarily used as a
smoke control device
to control the flow of
air in ductwork.

20
Initiating Devices

Manual Fire Alarm Stations
• Manually-operated
device used to initiate
an alarm signal
 Single Action Stations
require a single
operation to activate it.
Generally a pulling
down action.
 Dual Action Stations
require two distinct
operations. A set-up
and an activating
action.

21
Notification Appliances Types
• Audible - Horns, Bells, Sounders,
Sirens, Chimes, Speakers
• Visual - Strobes
• Physical - Bed shakers
• Olfactory - Smell

22
Audible Devices
• Bells: Used if they are
only for fire, or have a
distinctive sound from
other bell signaling
devices. Often used as
an external gong to
indicate the flow of
water in the sprinkler
system.
• Horns: Loud and
distinctive output.
Often used in highnoise environments,
such as manufacturing
plants.
23
Audible Devices
• Sounders: Electronic or
mechanical audible devices,
which are capable of producing a
variety of tones. Often, the tone
is selectable during installation of
the device.
• Chimes: Soft-toned appliances
used where loud noises could be
disruptive to other operations.
Generally used where qualified
personnel are continuously in
attendance.
24
Audible Devices
• Sirens: Extremely loud
devices generally
limited in use to
outdoor or heavy
industrial areas.
• Speakers: Audible
devices used in
conjunction with voice
evacuation messages.
Life-Safety speakers
are not generally
associated with Muzak
systems.
25
Visual Signaling
Appliances
Visual signaling appliances are
used in high-noise environments,
in areas occupied by hearingimpaired individuals, or in areas
where audible devices may not be
desired.

26
Visual Devices
Strobe
Chime/Strobe
Horn/
Strob
e

Speaker/
Strobe

27
The Fire Alarm
Systems

28
Types of Fire Alarm
Control Panels
• Conventional (hard wired)



Fixed
Programmable

• Addressable (multiplexed)
• Intelligent (analog data transfer)

29
Conventional “Hard Wired”
System
• Simplest type of control unit.
• Generally, a single circuit board contains power
supply, control, initiating and notification circuitry.
• Some models use auxiliary circuit boards to
perform special functions.
• Input/output devices connect to dedicated circuits.
• Designated outputs occur when initiating signals
are received.
• Limited special functions and capabilities.

30
Conventional “Programmable”
System
• Basic “Designed System”
• Components selected by the designer to
meet the direct needs of the customer.
• Initiating circuits are programmable for fire,
waterflow, supervisory service, etc.
• Output circuits are programmable for code
selection and silenceability.
• On some systems, input-to-output CIRCUIT
(not device) mapping.
31
Addressable System
• Each device (detector, pull station…) has a unique
number assigned to it called the address for
reporting alarms and troubles.
• Employs a Signaling Line Circuit (SLC) Loop along
which all addressable input and output devices are
connected to the fire alarm control panel.
• Addressable devices transmit an electronic
message back to the Control Unit representing
their state (Normal, Alarm, Trouble) when polled by
the Control Unit.

32
Analog System
• Always an Addressable System.
• Processes detailed, analog data from
detectors about smoke levels.
• Can provide sensitivity data for each
detector.
• Employs Drift Compensation (self
calibration) in its detectors.

33
Terminology
•
•
•
•
•
•
•
•
•
•
•
•

FACP - Fire Alarm Control Panel.
FACU - Fire Alarm Control Unit.
FCC - Federal Communications Commission
UL - Underwriters Laboratories
NFPA - National Fire Protection Agency.
AHJ, LAHJ - Authority Having Jurisdiction, Local AHJ
ADAAG - Americans with Disabilities Act Accessibility
Guidelines.
PoC - Products of Combustion
LED - Light Emitting Diode
IDC - Initiating Device Circuit
NAC - Notification Appliance Circuit
ELR, EOL - End of Line Resistor

34
Terminology
•
•
•
•
•
•
•
•
•
•
•
•

NEC - National Electrical Code (NFPA 70)
NEMA - National Electrical Manufacturing Association
EIA - Electronics Industry Association
Cd - Candela
dB, dBA - Decibels
FWR - Full Wave Rectified
ANSI - American National Standards Institute
PIV - Post Indicator Valve
OS&Y - Outside Stem and Yoke Valves
SFPE - Society for Fire Protection Engineers
Shall - Indicates a mandatory requirement
Should - Indicates a recommendation or advisement

35
References
•
•
•
•
•
•
•

NFPA 70 - National Electrical Code
NFPA 72 - National Fire Alarm Code
NFPA 101 - Life Safety Code
National Electrical Code Handbook, NFPA
Life Safety Code Handbook, NFPA
Fire Protection Handbook, NFPA
Fire Alarm Signaling Systems, NFPA

36
Basic Fire Alarm
Technology
Please visit
www.farenhyt.com for fire
alarm system solutions
for your facility

Silent Knight :: 7550 Meridian Circle :: Maple Grove, MN 55369 :: 800-328-0103

37

Intro to basic fire alarm technology

  • 1.
    Intro to Basic FireAlarm Technology Silent Knight :: 7550 Meridian Circle :: Maple Grove, MN 55369 :: 800-328-0103 1
  • 2.
    Basic Fire Let’s examinethe components that make a basic Fire Alarm Control System. 2
  • 3.
    Main Controller • Thebrains of the system • Provides power to the system, monitors inputs and controls outputs through various circuits • Performs other functions as required by the appropriate code 3
  • 4.
    Elements of aControl Panel Requires two Power Sources Primary (AC) Secondary (DC) 4
  • 5.
    Elements of aControl Panel Inputs A fire alarm system can have a variety of input devices. Smoke Detector Manual Pull Station 5
  • 6.
    Inputs • Initiating Device:A system component that originates transmission of a change of state condition, such as a smoke detector, manual fire alarm box, supervisory switch, etc... • Initiating Device Circuit (IDC): A circuit to which automatic or manual initiating devices are connected where the signal received does not identify the individual device operated 6
  • 7.
    Elements of aControl Panel Outputs Horns Strobes 7
  • 8.
    Outputs • Notification Appliance:A fire alarm system component such as a bell, horn, speaker, light, or text display that provides audible, tactile, or visible output, or any combination thereof. • Notification Appliance Circuit: A circuit or path directly connected to a notification appliance. 8
  • 9.
    The Basic System MainController Inputs Primary (AC) Outputs Secondary (DC) 9
  • 10.
    Basic Fire AlarmTechnology • Signal Initiation/Initiating Devices  Need to understand stages of fire and what technology works best for each 10
  • 11.
    The Stages ofa Fire • Stage One  Incipient: Products of Combustion particles are produced (<0.3 microns). No visible smoke or detectable heat. May occur for milliseconds or days. • Use ionization detectors 11
  • 12.
    The Stages ofa Fire • Stage Two  Smoldering: Visible smoke particles are produced (>0.3 microns). Little visible flame or noticeable heat. • Use Photoelectric Detectors 12
  • 13.
    The Stages ofa Fire • Stage Three  Flame: Rapid combustion produces radiant energy in the visible, and invisible (IR, UV) spectrums. Heat begins to buildup at this stage • Use Spark or Flame Detectors 13
  • 14.
    The Stages ofa Fire • Stage Four  High Heat: Uncontrolled combustion is caused by the heating of nearby combustibles to their ignition point. • Use Heat Detectors  Note! Major disadvantages of using thermal energy for fire identification are • Takes a while for a fire to be recognized • The toxic gases that are produced before an alarm point is reached 14
  • 15.
    Types of Detectors •Photoelectric   • • • Light Scattering Light Obscuration Ionization Duct Heat (Thermal) 15
  • 16.
    Photoelectric Smoke Detectors: Light-Scattering Type •Uses a Light-Emitting Diode (LED) that sends a beam of light into a dark chambera photo diode sits on the other side of a partition within the chamber   • Smoke particles entering the chamber deflect some of the light rays into the photo cell. The photo cell generates a current when exposed to light, and if the current reaches a certain level, the detector alarms. 16
  • 17.
    Photoelectric Smoke Detectors: LightObscuration Type • In a projected Beam Detector, alarms are generated by diffusing the projected light beam by a specified percentage of obscuration. • Total beam blockage generally results in a trouble signal. 17
  • 18.
    Ionization Smoke Detectors •Contain a small amount of radioactive material encapsulated in a metal chamber. Ionizing radiation develops a low, but steady electrical current.  Smoke particles entering the chamber disrupt the current and trigger the detector's alarm.  • Ion detectors react more quickly to fast flaming fires that give off little smoke. 18
  • 19.
    Heat Detectors • FixedDetectors:  Alarm when the sensing element reaches a certain set point.  Two common models have 135 and 200-degrees F range.  Fixed element is generally a non-restorable type, and when activated, must be replaced. • Rate-of-Rise Detectors:  Respond when the rate of temperature increase is greater than an allowable limit (15 degrees in 60 secs.) (placement in a stable environment) (e.g.. ovens, heating vents, etc.).  The Rate-of-Rise element is restorable when conditions return to normal. • Rate Compensation will respond regardless of the rate of temperature rise. 19
  • 20.
    Duct Detectors • Photoelectricdetector mounted in housing outside the ductwork that has probes that extend into the duct to sample the air inside the duct. • Primarily used as a smoke control device to control the flow of air in ductwork. 20
  • 21.
    Initiating Devices Manual FireAlarm Stations • Manually-operated device used to initiate an alarm signal  Single Action Stations require a single operation to activate it. Generally a pulling down action.  Dual Action Stations require two distinct operations. A set-up and an activating action. 21
  • 22.
    Notification Appliances Types •Audible - Horns, Bells, Sounders, Sirens, Chimes, Speakers • Visual - Strobes • Physical - Bed shakers • Olfactory - Smell 22
  • 23.
    Audible Devices • Bells:Used if they are only for fire, or have a distinctive sound from other bell signaling devices. Often used as an external gong to indicate the flow of water in the sprinkler system. • Horns: Loud and distinctive output. Often used in highnoise environments, such as manufacturing plants. 23
  • 24.
    Audible Devices • Sounders:Electronic or mechanical audible devices, which are capable of producing a variety of tones. Often, the tone is selectable during installation of the device. • Chimes: Soft-toned appliances used where loud noises could be disruptive to other operations. Generally used where qualified personnel are continuously in attendance. 24
  • 25.
    Audible Devices • Sirens:Extremely loud devices generally limited in use to outdoor or heavy industrial areas. • Speakers: Audible devices used in conjunction with voice evacuation messages. Life-Safety speakers are not generally associated with Muzak systems. 25
  • 26.
    Visual Signaling Appliances Visual signalingappliances are used in high-noise environments, in areas occupied by hearingimpaired individuals, or in areas where audible devices may not be desired. 26
  • 27.
  • 28.
  • 29.
    Types of FireAlarm Control Panels • Conventional (hard wired)   Fixed Programmable • Addressable (multiplexed) • Intelligent (analog data transfer) 29
  • 30.
    Conventional “Hard Wired” System •Simplest type of control unit. • Generally, a single circuit board contains power supply, control, initiating and notification circuitry. • Some models use auxiliary circuit boards to perform special functions. • Input/output devices connect to dedicated circuits. • Designated outputs occur when initiating signals are received. • Limited special functions and capabilities. 30
  • 31.
    Conventional “Programmable” System • Basic“Designed System” • Components selected by the designer to meet the direct needs of the customer. • Initiating circuits are programmable for fire, waterflow, supervisory service, etc. • Output circuits are programmable for code selection and silenceability. • On some systems, input-to-output CIRCUIT (not device) mapping. 31
  • 32.
    Addressable System • Eachdevice (detector, pull station…) has a unique number assigned to it called the address for reporting alarms and troubles. • Employs a Signaling Line Circuit (SLC) Loop along which all addressable input and output devices are connected to the fire alarm control panel. • Addressable devices transmit an electronic message back to the Control Unit representing their state (Normal, Alarm, Trouble) when polled by the Control Unit. 32
  • 33.
    Analog System • Alwaysan Addressable System. • Processes detailed, analog data from detectors about smoke levels. • Can provide sensitivity data for each detector. • Employs Drift Compensation (self calibration) in its detectors. 33
  • 34.
    Terminology • • • • • • • • • • • • FACP - FireAlarm Control Panel. FACU - Fire Alarm Control Unit. FCC - Federal Communications Commission UL - Underwriters Laboratories NFPA - National Fire Protection Agency. AHJ, LAHJ - Authority Having Jurisdiction, Local AHJ ADAAG - Americans with Disabilities Act Accessibility Guidelines. PoC - Products of Combustion LED - Light Emitting Diode IDC - Initiating Device Circuit NAC - Notification Appliance Circuit ELR, EOL - End of Line Resistor 34
  • 35.
    Terminology • • • • • • • • • • • • NEC - NationalElectrical Code (NFPA 70) NEMA - National Electrical Manufacturing Association EIA - Electronics Industry Association Cd - Candela dB, dBA - Decibels FWR - Full Wave Rectified ANSI - American National Standards Institute PIV - Post Indicator Valve OS&Y - Outside Stem and Yoke Valves SFPE - Society for Fire Protection Engineers Shall - Indicates a mandatory requirement Should - Indicates a recommendation or advisement 35
  • 36.
    References • • • • • • • NFPA 70 -National Electrical Code NFPA 72 - National Fire Alarm Code NFPA 101 - Life Safety Code National Electrical Code Handbook, NFPA Life Safety Code Handbook, NFPA Fire Protection Handbook, NFPA Fire Alarm Signaling Systems, NFPA 36
  • 37.
    Basic Fire Alarm Technology Pleasevisit www.farenhyt.com for fire alarm system solutions for your facility Silent Knight :: 7550 Meridian Circle :: Maple Grove, MN 55369 :: 800-328-0103 37

Editor's Notes

  • #4 Nicknames for the main controller. Main Board, Main Controller, Motherboard, Central Processing Unit (CPU) Also includes a user interface (keypad) and locked enclosure.
  • #8 A fire alarm system can have a variety of output devices
  • #10 This is it for a basic system. Anything else that might be needed is considered &quot;SUPPLEMENTARY&quot;
  • #18 Smoke obscures a normal linear path of light. Complete and solid blockage from say a ladder will generate a trouble. Beam detection may provide more cost effective solutions to point detection over long distances, especially when the buildings are relatively tall, or where excessive height excludes the use of point detection. Applications include large production facilities, warehouses, ceiling voids, above false ceilings, open areas of shopping malls, churches, aircraft hangers.
  • #21 Sometimes these devices are considered to be supervisory in nature rather than alarm. Why? Does an HVAC system run all the time? Remember that smoke inside the duct will be diluted, inducing a delay in response time for detection of an alarm.
  • #23 Notification Appliances are made for four of the five senses - hear, see, touch, smell (but not taste).
  • #25 Chimes - Used for PRIVATE MODE applications
  • #26 The DC siren shown (Federal Signal) gives off 127 dB at 100 ft!
  • #30 The history of fire alarm development - basic &quot;no frills&quot; panel through programmability, addressability and now intelligence.
  • #34 A system that is said to be INTELLIGENT or ANALOG has capabilities like those listed here. Top-of-the-line systems can make decisions about alarm conditions by using data from one or more input devices.
  • #35 This presentation includes a large number of acronyms and abbreviations. Let’s introduce some of the more common ones now.